Together, We Drive the Future
Home / Shore Power
MV EVFD NANCAL ELECTRIC
NC AMP Series
High voltage: 300kVA-20MVA
Low voltage: 40kVA-8MVA
Marine power supply​​​​​​​
Nancal Electric AMP Series
Shore Power
NC AMP Series Shore Power is a product used for the proven inverter technology of enterprise and provides power for ship docking.
In order to reduce the pollution caused by the port environment and noise, gas or diesel generator sets should be turned off during the shipment.
The output frequency of the shore power is 50 or 60Hz with output voltage 6 and 6.6kV designed for the AMP H series. 400/440V belongs to AMP L Series.
  • low harmonic vfd
    No Pollution

  • high power factor vfd
    Low Energy Cost​​​​​​​

  • THDI-TEST

    Seamless 

    Synchronous Transfer


  • 24h

     Stable Voltage

    Stable Frequency

     Sinewave Output​​​​​​​


Advantages
  • Single high-voltage cable connection, easy installation
  • High output power, delivering daily and routine power consumption during operations at berth
  • Synchronous transfer with the load without any influence on the marine devices
  • Automatic frequency stabilization and voltage regulation
  • Multiple output interfaces, powering multiple vessels simultaneously
 
Features
  • Comprehensive system protection
  • Select the voltage sampling signal of transformer secondary winding to achieve closed-loop voltage control and ensure the stability of output voltage under different loads
  • Multi-pulse rectifier reduces high order harmonic currents, meets IEEE519 standard
  • Fast dynamic response, fast recovery in case of sudden load fluctuation, recovery time <20ms
NC AMP H Series 
Medium Volatge Shore Power
Input
Voltage: 3 Phase, 3kV-11kV±10%
Frequency: 50Hz/60Hz±10%
Output
Voltage: 6kV/6.6kV (options)
Frequency: 50Hz/60Hz 
Capacity: 0-20000kVA
Overload Capacity: 120%≥1min
Waveform: Multi-level PWM, Sine wave
Performance
Input: THDi≤2%
Output: THDi≤2%
Efficiency: ≥97.5%
Power Factor: >0.98 (rated capacity)
MTTF: >50000h
Control
Control Method: Constant frequency
Voltage Output, Voltage Close Loop
Voltage Accuracy: 0.1%
Protections
Overvoltage, Overcurrent, Overloading, Transformer Overheating, Grounding error,
Fan error, Safety lock
Structure
Protection: IP31 standard(options)
Noise level: <70db
Cooling: Air/Water Cooling
Options: Containerized cabinet, Output isolation transformer, Junction box, Bypass cabinet
Environment
Environment: Indoor or outdoor with containerized cabinet
Temperature: -15℃~+40℃
Humidity: 95% without condensation
Interface
Profibus, Modbus, and etc.
  NC AMP L Series 
  Low Volatge Shore Power
Input
Voltage: 3 Phase, 380-690V±10%
Frequency: 50Hz/60Hz±10%
Output
Voltage: 400V/440V/480V
Frequency: 50Hz/60Hz 
Capacity: 0-5000kVA
Overload Capacity: 150%≥1min
Performance
Input: THDi≤3%
Output: THDi≤3%
Efficiency: ≥97%
Power Factor: >0.99 (Rated capacity)
MTTF: >50000h
Control
Control Method: Constant frequency
Voltage Output, Voltage Close Loop
Voltage Accuracy: 0.2%
Protections
Short circuit, Overvoltage, Overcurrent, Overloading, Undervoltage, Phase lose, Overheating
Structure
Protection: IP21 standard(options)
Noise Level: <70db
Cooling: Air Cooling
Options: Containerized cabinet, Output isolation transformer, Junction box, Bypass cabinet
Environment
Environment: Indoor or outdoor with containerized cabinet
Temperature: 15℃~+40℃
Humidity: 95% without condensation
Interface
Profibus, Modbus, and etc.
shore power-nancal